Installation
Important: This thermostat must be installed according to all national
and local electrical codes. The installation must be performed by
qualified personnel.
Locating the floor temperature sensor
The floor temperature sensor is installed under the floor surface. See
the QuickNet System Installation Manual (H57704),Section6,formore
details. Perform the Sensor Resistance Test prior to terminating the floor
sensor to the thermostat. See the QuickNet System Installation Manual
(H57704), Section 7, for more details.
Wiring the thermostat
WARNING: TURN OFF THE POWER TO THE CIRCUIT AT THE MAIN
POWER PANEL TO AVOID ELECTRIC SHOCK.
WARNING: SHOCK HAZARD. TO PREVENT SHOCK, THE QUICKNET
FLOOR HEATING MAT MUST BE CONNECTED TO GROUND.
1.Remove
thecontrolmodulefromthepowerbasebylooseningthe
captive screw underneath the base.
2.Connect
thefloor
heating cold leads to
the load wires (two
inner wires) using the
supplied wire nuts.
3.
Connect
thepower
supply leads to the
power base wires (two
outer wires) using the
supplied wire nuts.
4. Connect the floor
heating cold lead braid
(ground)tothesupplygroundintheelectricaljunctionbox.
5.Insert
thefloorsensorcablethroughoneofthetwoopeningsonthe
power base and connect to terminals 1 and 2 (no polarity). Position
the sensor cable such that it does not come in contact with the floor
heating wires.
6.Push
theexcesslengthofthewiresbackinsidetheelectricaljunction
box
7.Secure
thepowerbasetotheelectricaljunctionboxusingthe
provided mounting screws
8.Verify
thesettingsoftheconfigurationswitchesonthebackofthe
control module. Default settings for the configuration switches are
highlighted below.
Important: If your system is installed underneath laminate or
engineered wood flooring, you MUST use AF mode with the default
settings. Note the factory default is AF mode.
No. Configuration Up Down
1 Display format °F/12hr °C/24hr
2 Early Start
1
Enable Disable
3 Temperature control mode
2
F AF
1
EarlyStartcanbeusedinAutomaticmodeonly.Whenthisfunctionis
enabled, the thermostat calculates the optimal time to start heating in
order to obtain the desired temperature by the set time. The thermostat
re-assesses the start time daily based on the previous day’s results.
Note: If you wish to use only 2 periods, set periods “1 and 4” or
periods “2 and 3”. Early Start will not work if you set periods “1 and
2” or periods “3 and 4”.
2
To select floor sensing mode, place the switch to the F position. To
select floor sensing and ambient sensing mode, place the switch to
theAFpositionandensurethattheremotetemperaturesensoris
connectedtothethermostat.ToselecttheAmode,placetheswitchin
theAFpositionandensurethattheremotetemperaturesensorisNOT
connected to the thermostat.
9.Installthecontrolmoduleontothepowerbase.
Control
module
Air
vents
Air
vents
Power
base
QuickStat-TC Installation & Operation Manual
2
Power
supply
Load / Floor heating mat
Supply
ground
Floor heating
cold lead
ground
Floor temperature sensor
Supply ground
Floor heating
cold lead
ground
400-115-052